Articles 210 addresses "branch circuits" (as opposed to service or feeder circuits) and receptacles and fixtures on branch circuits. There are requirements for the minimum number of branches, and placement of receptacles, according to the location and purpose of the receptacle outlet. A ground fault circuit interrupter (GFCI) is required for all receptacles in wet locations, eg: outlets in bathrooms, outdoors and kitchens, and, in addition, for dwelling units: crawl-spaces, garages, boathouses, unfinished basements, and within 6 feet (1.8 m) of a wet-bar sink, with limited exceptions. See NEC for details. The NEC also has rules about such things as how many circuits and receptacles/outlets should be placed in a given residential dwelling, and how far apart they can be in a given type of room, based upon the typical cord-length of small appliances (for example, not more than 12 feet apart, or 4 feet apart on kitchen countertops).

Polarized, grounding, 120-volt receptacle

As of 1962 the NEC required that new 120-volt household receptacle outlets, for general purpose use, be both grounded and polarized. NEMA has implemented this in its U.S. standard socket configurations so that:

  • There must be a slot for a center-line, rounded pin connected to a common grounding conductor.
  • The two blade-shaped slots must be of differing sizes, to prevent ungrounded (2-wire) devices which use "neutral" as their only grounding from being misconnected.

The NEC also has provisions that permit the use of grounding-type receptacles in nongrounded wiring (for example, the retrofit of 2-wire circuits) if a GFCI is used for protection of the new outlet (either itself or "downstream" from a GFCI). Art. 406.3(D)(3).


www.homeinspectionservices.org
Category:
��
4:27 PM | Posted in

Because most conduit and cabinets are made from metal, it is common for these components to have sharp metal edges due to the manufacturing processes. The NEC specifies a number of protective measures to help protect wire insulation from being cut or damaged by these edges both during installation and later when in actual use. Insulated cables may not be inserted directly through knockouts, for example, due to the sharp edge around nearly all knockout holes. Clamping and other wire protection is often not required for plastic conduit parts, since the plastic is not likely to damage insulation in contact with it.

In potentially hazardous locations, more robust cable protection may be necessary. Common conduit and ductwork protects against direct physical abuse, but is neither airtight nor watertight. In wet locations, conduit may resemble standard threaded pipe in appearance, with sealed gasketed box openings to keep moisture out. Areas with potentially explosive gases need further protection to prevent electrical sparks from igniting the gases, and internal conduit gas-tight barriers to prevent potentially ignited gases from traveling inside the conduit to other parts of the building.


www.homeinspectionservices.org

Category:
��
4:11 PM | Posted in

Temperature rating

The temperature rating of a wire or cable is generally the maximum safe ambient temperature that the wire can carry full-load power without the cable insulation either melting, oxidizing, or self-igniting. A full-load wire does heat up slightly due to the metallic resistance to the current, but this wire heating is factored into the cable's temperature rating. (NEC 310.10)

The NEC specifies acceptable numbers of conductors in crowded areas such as inside conduit, referred to as the fill rating. If the accepted fill rating is exceeded then all the cables in the conduit are derated, lowering their acceptable maximum ambient operating temperature. This is necessary because when multiple conductors are carrying full-load power, there is a combined heating of all the cables that may exceed the normal insulation temperature rating. (NEC 310.16)

In construction situations where future expansion is highly likely to occur, it is sometimes economical to install a slightly larger diameter conduit than is necessary for the initial building construction. Larger conduit costs more money, but has a greater fill rating than smaller conduit, so that in the future no additional conduit installations may be required in order to add additional circuits while maintaining the conduit's overall temperature rating.

In certain special situations the temperature rating can be higher than normal, such as for knob and tube wiring where two or more load-carrying wires are never likely to be in close proximity. The single lone load wires suspended in midair in knob and tube wiring will have a greater heat-dissipation rate than the standard 3-wire NM-2 cable which includes two tightly bundled load and return wires.


www.homeinspectionservices.org

Category:
��
4:11 PM | Posted in

Actual vs maximum current rating

Nominal Rated
Circuit Capacity
Continuous Rated
Circuit Capacity
5 amps 4 amps
10 amps 8 amps
15 amps 12 amps
20 amps 16 amps
30 amps 24 amps
50 amps 40 amps
100 amps 80 amps
200 amps 160 amps

Most commonly available circuit breakers are rated to carry no more than 80% of their nominal rating continuously (3 hours or more) (NEC Art. 100). 100%-rated circuit breakers are manufactured for and may carry 100% of their nominal rating continuously.


www.homeinspectionservices.org
Category:
��
4:08 PM | Posted in

Conduit and cable protection

In home construction, wiring is commonly allowed to be installed directly in walls without further protection. However in commercial and industrial buildings, wire needs to be better protected from damage, and so it is more commonly installed inside conduit or ductwork made of metal, plastic, or passageways cast in concrete.

While some types of wiring are available already inside a protective flexible spiraled metal shell, it is more common for conduit and ductwork to be installed empty and the wire added later by threading it through the finished passageways. The NEC spends considerable time documenting safe methods of installing cable in conduit, with the primary concerns being the friction and abrading of insulation due to pulling, damage to the wires or insulation due to sharp bending and kinking, and damage due to too much pulling strain on the cable.

A wire pulled with excessive force may break inside the conduit, requiring costly removal and replacement of the damaged wire. However, a wire pulled with just enough force to stretch the wire but not break it creates a fire and future-failure hazard. The stretched wire section will have a thinner conductive cross-section than other parts of the cable, causing the stretched wire to heat more rapidly due to lower current-carrying capacity. The stretched wire insulation also becomes thinner, reducing the voltage needed to penetrate the insulation. Breaks may also form in the stretched insulation, which may not immediately be discovered until the circuit is powered and damage from arcing or shorting has occurred.

Because most conduit and cabinets are made from metal, it is common for these components to have sharp metal edges due to the manufacturing processes. The NEC specifies a number of protective measures to help protect wire insulation from being cut or damaged by these edges both during installation and later when in actual use. Insulated cables may not be inserted directly through knockouts, for example, due to the sharp edge around nearly all knockout holes. Clamping and other wire protection is often not required for plastic conduit parts, since the plastic is not likely to damage insulation in contact with it.

In potentially hazardous locations, more robust cable protection may be necessary. Common conduit and ductwork protects against direct physical abuse, but is neither airtight nor watertight. In wet locations, conduit may resemble standard threaded pipe in appearance, with sealed gasketed box openings to keep moisture out. Areas with potentially explosive gases need further protection to prevent electrical sparks from igniting the gases, and internal conduit gas-tight barriers to prevent potentially ignited gases from traveling inside the conduit to other parts of the building.


www.homeinspectionservices.org

Category:
��
3:55 PM | Posted in

The NEC is available as a bound book containing approximately 1000 pages. It has been available in electronic form since the 1993 edition. The code is updated every three years. However, some jurisdictions do not immediately adopt the new edition.

The NEC is also available as a restricted, digitized coding model that can be read online free of charge on certain computing platforms. An external link to this online access is referenced at the end of this article.

In the United States, statutory law cannot be copyrighted and is freely accessible and copyable by anyone.

When a standards organization develops a new coding model and it is not yet accepted by any jurisdiction as law, it is still the private property of the standards organization and the reader may be restricted from downloading or printing the text for offline viewing. For that privilege, the coding model must still be purchased as either printed media or a CD-ROM.

Here is a link to California adopted codes.

http://bulk.resource.org/codes.gov/ca.local/